July 26, 2011

Efficiency in UPSes - Part 2

Continuing from last post on Efficiency...

Besides Power Factory Efficiency, the other type of Efficiency is Topology Efficiency.

This type of Efficiency is more related to energy savings, but honestly more gimmicky as manufacturers tout their green credentials.

Simply put, Topology Efficiency is the amount of energy used to operate the UPS.  Lets recall Topology... Its is the method of providing backup power.  Online Topology, is simply that its allways online.. allways giving you clean power.  Line Interactive Topology uses a 'switch' to turn on the UPS power if something in the line goes bad.  Obviously, Online - since its always on - will use more energy than a line interactive that just turns on when needed.


So line interactive UPSes are more efficient than online types can ever be.   Within the Line Interactive model mix, there are a few super efficient models.  The APC 5th generation units, (like the 200v) dont switch over to the energy intensive UPS power, unless its really necessary.  Some sort of magic corrects alot of the minor power problems without energizing those line interactive transformers.  Older units, didnt really care, and just switched over - saying to hell with a few watts.

And thats the problem... this super efficient line interactive UPS like the 5th gen APC save so little power, thats its kind of stupid.  The idea that saving of 5 kWh ($1) a month when your server room is set at 60 degrees and you are running 10,000 watts of servers is pointless.  Its like ordering a Diet Coke with a Bacon Double Big Mac, Fries, Milkshake and a bucket of lard.

Bottomline, the Topology of the UPS dictates its efficiency by determining how often the unit runs.

July 22, 2011

Efficiency in UPSes - Part 1

Efficiency is a great buzzword today, but has several meanings in the UPS world.  None of the definitions reflect what most people think of when they buy fuel efficient car, or energy efficient light bulb.

Definition 1 - Power Factor Efficiency
As I have said before, UPSes are sized in Volt Amps (VA).  While the actual Wattage is usually a factor of that VA, depending on the UPS.
A 1000va UPSes can offer 900, 670, or even 500watts, depending on its Power Factor efficiency .  Larger and even more expensive units can have the same apparent low efficiency.  The $3500 SURTD5000XLT has a 70% Power Factor Efficiency, delivering 3500watts per 5000va unit.   The MGE 5kva unit is really efficient in Power Factor, as it delivers 4500watts per 5000va unit.  Whereas, the Symmetra PX UPS is 100% efficient, delivering 10kw per 10kva.

Bottomline, while this is the most important spec in UPSes, the lower power factor efficiency doesn't necessarily mean that a unit is wasting energy like our common sense of efficiency..

October 10, 2011

Random Part of the Month XIII - QWPAEFFICIENCY-MISC

While APC makes most of their money on products... like everyone else they are now expanding aggressively into services.

This product, the QWPAEFFICIENCY-MISC  is actually a ~$3750.00 report based on the physical site survey of your data center.   The report focuses on efficiency and eliminating waste   (I guess paying nearly $4000 isnt waste to them)  Some of the nuggets of value

  • Reports efficiency values for the data center.
  • Identify the air distribution methodology.
  • Provide projected efficiency improvements for each recommendation to facilitate ROI calculations and capital expenditure justification.
  • Using the data center one-line diagram, create a list of all measurements required to accurately characterize the power use of the data center infrastructure elements.

Sign up for some of the other APC services here

October 24, 2010

What are the Important Specs in comparing UPS units

This week a customer sent me a spec page for a UPS brand I had never heard of  (ProVar 5000, or something).  While spec pages have hundreds of features, there are 4 to concentrate on


UPS Technology  -  Today there a 2 types, Line Interactive or Online/Double Conversion.  Online provides the cleanest power and is generally a lot more money.  If the existing spec is Online, its only fair to compare a similar model.  But it is often over requested.


VA/Watts - These are the UPS's electrical capacity.  The VA is often part of the model number and headline spec.  The watts can be 90%, 80% or 70% of that value depending on the units Efficiency.  So, if someone asks for a high efficiency 2200va capacity unit, I will probably spec a 3000va, to get their desired watts just because upgrading to a high efficiency unit is more than upgrading the VA.

Voltage - Tthis is where the spec pages can get you in trouble.  120volt is simple, but higher voltages are much more complex.  There is big difference between Voltage Range and Nominal Voltage.  Ignore the Voltage Range on the spec. UPSes are pre-set to accept 208, 220, 230, and/or 240v.   A 208v system wont  work on 230v and vice versa.  Also, UPSes cant normally change the power.  If you want 230v output and have only 208v at your building, you can't buy a 230volt UPS.  Nearly every commercial building in the US has 208volt.  Rarely would you have 240 or anything else.   Look at my last post about how we have managed the different types


Plugs and Ports -  All input plugs can be changed to match your needs.  The backplate or output receptacles can generally be changed as needed.  So the only port that is important, is the XL or Extended Run port.  Nearly every unit (except those made by APC) has a port to add extra battery packs to to add runtime. Like the Online spec, its important to make sure customers know they are usually paying 10-25% more for this feature.


As for the remaining specs, most aren't critical and usually match among manufacturers.  Frequency, Crest factor, BTus, Environmental, Surge Protection, Wave form, are all about the same for a given UPS size and type.

Two other factors, physical size and runtime, usually can be handled once a particular model has been chosen.      Smaller units usually cost more, and runtime is completely dependent on battery size.  

September 1, 2014

Best of the Blog 2009-2014 - Advice I

Resuming blogging in 2014, its probably wise to highlight the best posts from the last few years.

Re-reading them now, its clear that some should never be mentioned again.   But here are the truly valuable ones or at least not completely full of BS.

Best Advice Posts



Worst Analogies

  • Dell's High Efficiency Online units being the essence of the universe
    • Dell's High Efficiency Online UPS is a hybrid of them all.   It has online isolating features when you need them and line interactive features when you dont.  If the balancing rock is the moderating line interactive and the lone tree in field is the isolating online.. then maybe this image is the combination:.finite and lonely but bearing the entire human species through the oceans of space and time.

January 15, 2010

New APC Line


Our friends at APC have launched the next generation of SmartUPS units featuring green energy efficient technology.

Their press releases tout these advantages

  1.  Increased intelligence that makes management and monitoring easier 
  2.  Increased efficiency that saves on utility costs
  3.  Increased control with ability to configure locally or via software and switched receptacle groups
  4.  Increased resilience with better diagnostic capabilities and improved warranty

Obviously, 1 and 3 have been desperately needed for awhile now, but 2 and 4 are a bit optimistic.

Increased efficiency alledged comes from the better handling of voltage regulation without using the energy intensive transformers.  Even APC admits this might only save 1-4%.  Hardly a “green” product.

As for resilience and batter warranty.  I don’t know about all units, but increasing from 2 to 3 years is still just the industry standard and not really that notable.  Further, with this new “Smart” LCD screen telling you how many days you have left before you need to change the battery, it sounds like a good racket to make you buy batteries before you need them

Anyway, we cant wait for the 5th generation of SmartUPS units to be fully rolled out.  APC needed this new launch to counter the dramatic improvements that Powerware and Tripplite have made in the last few years.



For more info here is their Youtube peppy video

And their press thingy

February 21, 2013

Dell UPS.. the Smarter UPS: 3 types of UPSes in 3 words


We have reviewed the several types of  UPS topology previously.  Standby, Line Interactive and Online Double Conversion are the most common.

All of these Topologies are just processes for which the UPS delivers backup energy and power conditioning.  However, many people get confused with these terms.

Dell has a nice succinct summary....



  • Standby - SWITCHES.  If there is a problem, it switches over to clean battery power
  • Line Interactive - MODERATES.  If there is a problem it first moderates the power by bucking or boosting the power to meet the equipment's needs.  This is why this this often called Smart
  • Online - ISOLATES.  If there is a problem, it doesn't care because power problems are fully isolated from the power system
Dell's High Efficiency Online UPS is a hybrid of them all.   It has online isolating features when you need them and line interactive features when you dont.  If the balancing rock is the moderating line interactive and the lone tree in field is the isolating online.. then maybe this image is the combination:.finite and lonely but bearing the entire human species through the oceans of space and time.


"On a mote of dust, suspended in a sunbeam" - Carl Sagan






January 26, 2011

Rumble in the Rack I - APC 593g4 versus MGE mx593

APC SmartUPS Online 5000va (SURTD5000XLT) 
versus 
MGE Pulsar MX 5000va (87050)
 v. 
They both have:

  • 5000va Double Conversion Online in a 3U frame
  • 208 and 240volt options
  • 4 output receptacles
  • XL feature for extended run
  • Rack or tower formats

The APC has:

  • more battery capacity to start
  • greater efficiency at (91%) full load
The MGE has:
  • More voltage options 220, 230
  • More wattage 4500watts (versus 3500watts)
  • LCD Display
  • Hardwire output
  • Modular interconnect-ability to 10kva
WINNER - MGE Pulsar MX

May 13, 2013

newsLightUPS Volume 1

As some have you experienced, we include a variety of items in our orders. Sometimes its sunflower seeds, or a granola bar or mint candy....
But now, we are including a flyer about some specials in a newsletter called newsLightUPS

The first edition is out and can viewed here or downloaded as a PDF.

Efficiency, Dells, Overstock and Surplus batteries were featured in this issue.

February 1, 2015

5PX Products Arrive

Eaton's latest line interactive units, the 5PX series is starting to come to the refurbished marketplace.

The Eaton 5PX Rack/Tower UPS with a next-generation intuitive LCD display, energy consumption metering down to the outlet group level, and up to 99% efficiency, the 5PX is the perfect UPS to protect modern IT equipment.

I like a few things about the 5PX.  They have great yield (1440watts @ 1500va) and the simple rack/tower switch is a nice touch.   Plus having all models extended run (even if they bring back the dreaded 5start connector cable) is great.  Finally, keeping the 3kva at 72volt now makes it an attractive option compared the 120vdc rating of the APC XL series.

GreenLightUPS has several models in stock:  30000va, 1500va and New models as well.



March 4, 2013

6000, 6000, 6000 ... Cant get enough?

I know I mentioned way back, that the APC 6000 3U unit was a great model... it has the L630P plug, net card and rail kit included, true online, and a small 3U frame...


But its getting crazy... in that everyone is asking about, repairing and buying them.

While thats fine.. we wanted to remind you of some BETTER buys in the 6kva range AND what makes them better


Dell Smarter LCD 6000 (eO694)

  • Blue LCD with full control
  • 200 to 240volt rated  
  • Online Double Conversion w/high efficiency mode
  • 10sec rail kit
  • more here

Liebert 6000va GXT 3 (lx695)

  • Arguably the best Online UPS manufacturer
  • 150% rated overload for those peak energy needs
  • More runtime 

Tripplite 6000va 6U (to696)

  • Great price
  • Twice the runtime as the 693g4
  • Free Network card included
  • $300 less than 693g4

Powerware 6000va (p9695)

  • Best 6kva value
  • More than twice the runtime
  • $400 less


APC 7500va 6U (796g3).

  • 1500va more power
  • Twice the battery of the 3U 6000va
  • Just $150 more for equivalently bundled unit (ask for 796g4)



February 19, 2011

More Sizing UPS challenges

Here is another case of nameplate sizing of equipment.  
I got a request for a UPS to power a fridge that uses 7.5amps that will last 4 hours.
7.5amps times 120volt is 900volt amps or va.   But thats not the whole story.....

Step one is to understand the amperage value and its meaning for the size of the UPS.   There are 4 "types" of amperages
  • FLA or full load amps or nameplate amperage  (this is usually on the equipment by the manufacturer)  It is used to size the circuitry.   That amperage never happens in real life.
  • SLA or starting load amps or the peak load that occurs just briefly during startup (depending on the motor, this can be 2 to 10 times the FLA)
  • RLA or running load amps  (this is the average amperage during operation)
  • RMS Amps or Observed amps  (this is when someone actually measures the amperage during the equipment's operation)
So,  7.5amps  is probably the FLA and the SLA on a new high efficiency equipment is about 15amps. (15a x 120v = 1800va).  So any 3000va UPS will work 

Step two is to understand the actual load over the 4 hour outage period.  Fridges cycle on and off, so getting an observed amperage is critical.  Factoring in the duty cycle of on and off over a 4hour period suggests the RLA is about 4.5amps.  Converting to wattage, suggests this fridge uses 430 watts.

Bottomline, left to his devices he might of gotten a 900va UPS with a trunk of batteries, but by understanding is real load meant he got what he needed for about half the price.

  

December 5, 2009

Mea Culpa Dixi - Slow shipping


A new series begins... Mea Culpa Dixi  (My faults spoken and settled)
In this occasional blog, I will address a complaint or disappointment that has come up and explain my position.

Complaint #1 - Slow Shipping
Your order a unit, but may not arrive for 14 days.

Absolutely true and I am truly sorry for the delay.  but here are the facts.

When we receive an order it goes through these steps.
  1. Invoices & work ticket printed
  2. Shipping arrangements researched & booked
  3. Unit is pulled from inventory
  4. Batteries are loaded, unit is charged
  5. Unit is tested, Unit is cleaned, Unit is recharged
  6. Unit is packed on a palleted and freight company is contacted
  7. Freight is picked up and shipped to a local freight terminal
  8. Freight company delivers freight
While sometimes this process can take 3 days, it more often takes close to 10 days.   Yet,  several problems during the process  including a non commercial address on order (during step 2),  low inventory of batteries (in step 4), unit fails testing (step 5); or the shipper doesn't have a phone number for delivery (in step 8) can add many days to the process.

We wish we were a large outfit that had Amazon.com efficiency, but we aren't.  One of our goals in 2010 is to streamline the process and get orders out faster.

For those that have been disappointed with the fulfillment times, we are sorry... mea culpa, Dixi

-Bob

October 23, 2009

120volt versus 208volt


If you can have either, what should it be?

I always recommend 120volt. But....
Choose 208volt for dense server racks that need a lot of power. 208volt provides more Uumph per outlet. (U/o) The main disadvantages are that 208volt units are more money and not all computer equipment can run on 208volt .

However, APC disagrees. Their white paper makes an argument for increased efficiency by going to 208volt . While it is true that units draw less current (amps) when you increased voltage (from 120v to 208) and hence cause less heat... its a paltry amount.

I told a customer recently, that I bet him leaving the light on in the server room causes more heat loss than the savings from 208volt to 120v. I suspect I will get an email from someone shortly proving me wrong.